Sign In | Join Free | My insurersguide.com
China Knkong Electric Co.,Ltd logo
Knkong Electric Co.,Ltd
Knkong Electric Co.,Ltd
Active Member

5 Years

Home > Gas Insulated Switchgear >

630A 12KV GIS Circuit Breaker Switchgear With VCB Unit

Knkong Electric Co.,Ltd
Contact Now

630A 12KV GIS Circuit Breaker Switchgear With VCB Unit

Brand Name : Knkong

Model Number : SF6 GIS HXGN15-12 Circuit breaker unit

Certification : IEC ISO GB

Place of Origin : China

MOQ : 1

Payment Terms : L/C, T/T

Supply Ability : 100 Unit per month

Delivery Time : 30 days

Packaging Details : Standard export packaging

Working Voltage : 12KV

Working Current : 630-1250A

Working Frequency : 50/60Hz

Type : Circuit breaker unit

OEM/ODM : Please share your CDA drawings

Manufactory : KNKONG

Contact Now

GB ISO 12KV Gas Insulated Switchgear Medium Voltage Ring Main Unit

Product Introduction

General

VCB unit, as known as V-unit has vacuum bubble, uses for breaking short-circuit current, one double-position disconnecting switch
is connected in series with the circuit breaker.
When the disconnecting switch at open position, the interlocked earthing switch can be closed to ground the cable cassing.
The operation between the VCB and the disconnecting switch, and the operation between the disconnecting switch and the
earthing switch are mechanically interlocked.

Service environment

  • Air temperature: -35℃~+40℃
  • Humidity: Monthly average 95%; Daily average 90%.
  • Altitude:≤ 1000m (Up to 5000 m can be custom)
  • Ambient air not apparently polluted by corrosive and flammable gas, vapor, etc.
  • No frequent violent shake

Technical Data

No. Item Unit Parameter
1 Rated voltage kV 12 24 36
2 Rated frequency Hz 50/60
3 Rated current A 630(1250*)
4

1min Power frequency

withstand voltage

wet kV 38 50 70
dry kV 48 60 85
5 Lightning impulse withstand voltage kV 75 125/150 170
6 Rated short circuit breaking current (peak) kA 80 63 63
7 Rated active load and close circuit breaking current A 63 50 50
8 Rated transferring current A 1700 1200 1200
9 Rated short circuit making a current (peak) kA 80 63 63
10 Rated cable(line) charging breaking current A

50 and 10

50/10

11 Cable charge breaking current in earthing fault A 20 20 20
12 Rated withstand current (peak) kA 80 63 63
13 Short-time withstand current (2s) kA 25 20 20
14 Mechanism life times 5000 2000 2000

Note: For short circuit breaking and the peak current is based on Fuse plus combination

Optional components:
Electric operating-AC 220/110V; DC 24/48/110/220V
Auxiliary contact 5 NO 5 NC
Full set of fuse
FTU communication interface

630A 12KV GIS Circuit Breaker Switchgear With VCB Unit


Product Tags:

GIS Circuit Breaker Switchgear

      

12KV Circuit Breaker Switchgear

      

630A Circuit Breaker Switchgear

      
Cheap 630A 12KV GIS Circuit Breaker Switchgear With VCB Unit for sale

630A 12KV GIS Circuit Breaker Switchgear With VCB Unit Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Knkong Electric Co.,Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)